Potter PAD300-DUCTR Analog Addressable Duct Detector, One form Relay, Compatible with Addressable IPA and AFC/ARC Series Panels, Gray and clear finish
Potter PAD300-DUCTR Analog Addressable Duct Detector, One form Relay, Compatible with Addressable IPA and AFC/ARC Series Panels, Gray and clear finish
Potter PAD300-DUCTR Analog Addressable Duct Detector, One form Relay, Compatible with Addressable IPA and AFC/ARC Series Panels, Gray and clear finish
PAD300-DUCTR | PL-PAD3DUCTR
Please sign in to view pricing and availability and to add to cart.
Product Overview
The PAD300-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two (2) tubes which protrude into the duct. An exhaust tube of one (1) standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined, the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and two (2) sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by four (4) capture screws.
Main Features
- Detects Smoke in Building HVAC Ducts
- SLC Class A, Class X & Class B
- No Screens or Filters in Housing
- Detects Smoke in Building HVAC Ducts
- Ships Complete with Housing and Head
- Compatible with Addressable IPA and AFC/ARC Series Panels
- Installation Without Removing the Head
- Listed Air Velocity of 100' to 4,000' per minute
- Durable Plastic Enclosure and Clear Cover
- Compatible with Supervised PAD100-DRTS Remote Test Switch, MS-RA, MS-KA/R, MS-KA/P/R Remote Indicators
General Information
Specifications
-
ADI Part Number PL-PAD3DUCTR Brand Name Potter Electric Signal, LLC Manufacturer Potter Electric Signal, LLC Manufacturer Part Number PAD300-DUCTR Product Model PAD300-DUCTR Product Name Analog Addressable Duct Detector Product Type Smoke Detector
-
Addressable Yes Connectivity Technology Wired Detectable Medium Fire, Gas Maximum Air Velocity 20.32 m/s Sensing Technology Photoelectric
-
Status Indicators Alarm, LED
-
Application/Usage Building, Commercial, HVAC, Industrial, Residential Color Gray Height 2.3" Product Color Clear, Gray Product Material Plastic Weight (Approximate) 2 lb Width 4.5"
-
Input Voltage 24V DC Power Source DC
-
Length 13.5"
-
Limited Warranty 5 Year
-
Certifications & Standards UL Listed Compatibility Potter Addressable IPA and AFC/ARC Series Panels Package Contents - Analog Addressable Duct Detector
- Installation Kit
- 1 x 7" Exhaust Tube
- 2.5ft Sampling Tube
- 5ft Sampling Tube
- 10ft Sampling Tube
- 2 x Sheet Metal Screw
- 4 x Capture Screw
UL Listed Yes