adi-insite-us
ADI US App
ADI Global Distribution
ADI a Resideo company
menu
content loaded
Altronix AL1024ULACMCBJ Access Power Controller with Power Supply/Charger, 8 PTC Class 2 Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure
Altronix

Altronix AL1024ULACMCBJ Access Power Controller with Power Supply Charger, PTC Class Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure

AL1024ULACMCBJ|AX-1024UACBJ
Altronix

Altronix AL1024ULACMCBJ Access Power Controller with Power Supply Charger, PTC Class Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure

AL1024ULACMCBJ|AX-1024UACBJ

Sign In for Dealer Pricing

Become an ADI Customer
Altronix AL1024ULACMCBJ Access Power Controller with Power Supply/Charger, 8 PTC Class 2 Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure
Altronix

Altronix AL1024ULACMCBJ Access Power Controller with Power Supply Charger, PTC Class Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure

AL1024ULACMCBJ | AX-1024UACBJ

Please sign in to view pricing and availability and to add to cart.

Overview
Specifications
Documents

Product Overview

These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. These power outputs can be converted to dry form "C" contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. Input Input 115VAC 60Hz rated @ 4.2A. Power supply input options: a) One (1) common power input for ACM8CB and lock power (factory installed). b) Two (2) isolated power inputs - One (1) to power the ACM8CB and one (1) for lock accessory power (external power supply is required). Current is determined by the power supply connected, not to exceed a maximum of 10A total). Eight (8) Access Control System trigger inputs. Input options: a) Eight (8) normally open (NO) inputs. b) Eight (8) open collector inputs. c) Any combination of the above. Output 24VDC @ 10A supply current. Class 2 Rated PTC protected power limited auto-resettable outputs. Eight (8) independently controlled outputs. Output options: Eight (8) Fail-Safe and/or Fail-Secure power outputs. Eight (8) auxiliary power outputs (unswitched). Output ratings PTCs are rated @ 2.5A. Filtered and electronically regulated outputs (built-in power supply). ACM8CB board main fuse is rated at 10A. Supervision AC fail supervision (form "C" contacts). Notification trigger is selectable for 30 seconds (factory set) or 6 hours. Low battery and battery presence supervision (form "C" contact). Features Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs. Fire Alarm disconnect input options: a) Normally open (NO) or normally closed (NC) dry contact input. b) Polarity reversal input from FACP signaling circuit. Alarm output relay indicates that FACP input is triggered (form "C" contact rated @ 1A 28VDC not evaluated by UL). Short circuit and thermal overload protection. Visual Indicators Red LEDs indicate outputs are triggered (relays energized). Green LED indicates FACP disconnect is triggered. AC input and DC output LED indicators. Battery Backup Built-in charger for sealed lead acid or gel type batteries. Automatic switch over to stand-by battery when AC fails. Zero voltage drop when unit switches over to battery backup (AC failure condition). AC fail supervision (form "C" contact). Battery fail and battery presence supervision (form "C" contact). Temperature Operating 0ºC to 49ºC (32ºF to 120ºF). Storage - 20ºC to 70ºC ( - 4ºF to 158ºF). Relative Humidity 85% +/- 5%. BTU/Hr. (approx.): 123 BTU/Hr.

Main Features

  • 8 PTC Class 2 Relay Outputs
  • Short circuit and thermal overload protection.
  • AC fail supervision & Battery fail and battery presence supervision (formin.C" contact).
  • Input 115VAC 60Hz rated @ 4.4 amp
  • Filtered and electronically regulated outputs

General Information

Name: Altronix AL1024ULACMCBJ Access Power Controller with Power Supply Charger, PTC Class Relay Outputs, 24VDC at 10A, FAI, 115VAC, BC600G Enclosure
Category: Altronix, Access Control, Batteries & Power Supplies, Power Products, Power Supplies & Boards, Access Power Controllers, Access Power Controllers
UPC Code: 782239937943
Country of Origin: US. Country of origin is subject to change.

Specifications

Product Documents and Resources