Potter PAD200-PD Analog Addressable Photoelectric Smoke Sensor (Replaces PAD100-PD)
Potter PAD200-PD Analog Addressable Photoelectric Smoke Sensor (Replaces PAD100-PD)
Potter PAD200-PD Analog Addressable Photoelectric Smoke Sensor (Replaces PAD100-PD)
PAD200-PD | PL-PAD200PD
Please sign in to view pricing and availability and to add to cart.
Product Overview
The Photoelectric Smoke Sensor is a listed Analog Addressable smoke sensor compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD200-PD is a low profile smoke sensor with a wide sensitivity range. The sensor and base (not included) are made of a durable plastic in an off-white color to blend in with the ceiling.
The PAD200-PD has a sensitivity range of 1.0 to 3.7 % per foot and is UL. The PAD200-PD features drift compensation and has built in dirty detector warning as well as. The PAD200-PD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements.
The sensor is compatible with any of the PAD series sensor bases and simply twists on. The PAD200-PD is addressed using DIP switches in the rear of the sensor and can be easily programmed in the field without special tools.
Compatible Bases
All bases will mount on a single gang, double gang, octagon, 4” square or mud ring electrical box.
- PAD100-4DB 4” Standard Base 3992731
- PAD100-6DB 6” Standard Base 3992732
- PAD100-IB 6” base with an isolator module included. 3992730
- PAD100-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992728
- PAD100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729
- PAD100-SPKB 6” base with speaker included 3992762
Main Features
- Legacy Unit; Latest Model is PAD300-PD
- UL 268 7th Edition
- Low profile, less than 2" with the base
- Wide selectable sensitivity range of 1.0 to 3.7%/foot
- Sensor communicates sensitivity to control panel
- UL listed smoke calibration and sensitivity
- Optional locking tab to prevent unwanted removal
- Simple DIP switch address setting, no programming tool required
- LED alarm indicator
- Product includes a 5 year warranty
General Information
Specifications
-
ADI Part Number PL-PAD200PD Brand Name Potter Electric Signal, LLC Manufacturer Potter Electric Signal, LLC Manufacturer Part Number PAD200-PD Product Model PAD200-PD Product Name Photoelectric Smoke Sensor Product Type Smoke Detector
-
Addressable Yes Connectivity Technology Wired Detectable Medium Fire, Smoke Sensing Technology Photoelectric Sensor Type Photoelectric, Thermal
-
Status Indicators Alarm, LED
-
Operating Relative Humidity (H-H) 0-93% Operating Temperature (T-T) 0-49 deg C
-
Color White Form Factor Ceiling Mount Height 1.4" Weight (Approximate) 3.56 oz
-
Input Voltage 24V DC
-
Diameter 3.9"
-
Limited Warranty 5 Year
-
Certifications UL 268 Features LED alarm indicator, Low profile, less than 2 inches with the base, Optional locking tab to prevent unwanted removal, Product includes a 5 year warranty, required, Sensor communicates sensitivity to control panel, Simple DIP switch address setting, no programming tool, UL 268 7th Edition, UL listed smoke calibration and sensitivity, UUKL Listed for Smoke Control, Wide selectable sensitivity range of 1.0 to 3.7%/foot UL Listed Yes