The FX-IDCWS connects normally open waterflow alarm and supervisory initiating device circuits (IDCs) to the Kidde control panel.
The FX-IDCWS is designed for Class B circuit operation.
The device address is set using the two rotary switches located on the front of the module. Two consecutive addresses are required.
The second address is automatically assigned one number higher that the value set on the rotary switches.
The FX-IDCWS can operate in the following modes:
Waterflow
- Alarm latching delayed: Configures the module for use with only nonretarded waterflow alarm switches. When the NO input contact of an initiating device is closed, an alarm is sent to the control panel, which after a 16 second time delay,generates an alarm signal.
Supervisory
- Supervisory active nonlatching US marketplace
- Supervisory active latching Canadian marketplace
- Nonlatching: Configures the module for normally open dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.
- Latching: Configures the module for normally open dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.
Main Features
- Analog Dual Input Waterflow, Supervisory Module- Used to connect normally open waterflow alarm and supervisory initiating device circuits to the FireworX control panel. For Class B circuit operation.
- Class A-B Two-Wire Module Acts as an interface between conventional two-wire smoke detectors and the Kidde control pane
- Analog Class A Single Input Module Used to connect a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit to the Kidde control panel
- Analog Dual Input Module Connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits to the Kidde control panel
- Analog SLC Fault Isolator Module Protects a Class A SLC from total collapse due to wire-to-wire short circuits
- Analog NAC Module Connects a supervised output circuit to a signal riser
- Analog Contact Relay Module Provides one Form C dry relay contact and can be configured to provide polarity reversal of its output
- Analog Single Input Mini Module Connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Kidde control panel. For Class B circuit operation
General Information
Name: Kidde FX-IDCWS Dual Input Waterflow, Supervisory Module
Category: Kidde Commercial, Fire, Fire Control Panels, Control Panel Modules
UPC Code: 793016036612
Country of Origin: China. Country of origin is subject to change.
Specifications
-
ADI Part Number ED-FXIDCWS Brand Name Kidde Commercial Manufacturer Carrier Manufacturer Part Number FX-IDCWS Product Model FX-IDCWS Product Name Dual Input Waterflow, Supervisory Module Product Series FX Product Type Waterflow Supervisory Module Â
-
Device Supported Control Panel Â
-
Maximum Operating Temperature 120.2°F (49°C) Minimum Operating Temperature 32°F (0°C) Â
-
Compatibility Kidde FX Series Control Panels Â